DSE9470 MKII
24 Volt 10 Amp Intelligent Battery Charger
UL RECOGNISED (USA & Canada) - NFPA 20 (QWIR2) COMPLIANT
The DSE9470 MKII is a UL recognised intelligent switch-mode battery charger that can be programmed for different charging curves. This helps to maximise battery life. The charger is programmed using the DSE Configuration Suite Software. The charger can be DIN rail or chassis mounted and has three built-in LEDs to indicate current charging status and fault conditions. The charger continues to operate during cranking and running and accepts multiple AC voltage connections.
70 mm x 200 mm x 130 mm (2.7” x 7.9” x 5.1”)
WEIGHT
0.75kg
PRODUCT VARIANTS
9470-01 - 24 V 10 A Intelligent Battery Charger (USA - UL - 110 V - 250 V)
9470-A4 - 24 V 10 A Intelligent Battery Charger (USA & Canada - UL - 110 V - 150 V)
SPECIFICATION
AC SUPPLY
VOLTAGE RANGE
90 V to 305 V (L-N)
FREQUENCY RANGE
48 Hz to 64 Hz (L-N)
DC OUTPUT
DSE9470 OUTPUT
10 A DC at 24 V DC
RIPPLE AND NOISE
<1%
EFFICIENCY
>86%
REGULATION
LINE
<0.5%
LOAD
2%
TEMPERATURE SENSOR INPUT
PT1000
PROTECTIONS
Short Circuit
DC Over Voltage
DC Over Current
Reverse Polarity
Over Temperature
AC Under & Over Voltage
CHARGE FAILURE RELAY
3 A at 30 V DC volt free relayDSE9473
24 volt, 15 amp Intelligent Battery Charger
80 mm x 205 mm x 135 mm (3.1" x 8.1" x 5.3")
WEIGHT
0.88 kg
PRODUCT VARIANTS
9473-01 - 9473 24 volt 15 amp Intelligent Battery Charger (90-305v 50/60Hz)
SPECIFICATION
AC SUPPLY
VOLTAGE RANGE
90 V to 305 V (L-N)
FREQUENCY RANGE
48 Hz to 64 Hz (L-N)
DC OUTPUT
DC OUTPUT
15 A DC 24 V DC
RIPPLE AND NOISE
1%
>90%
REGULATION
LINE
<0.5%
LOAD
2%
TEMPERATURE SENSOR INPUT
PT1000
PROTECTIONS
Short CircuitDC Over Voltage
DC Over Current
Reverse Polarity
Over Temperature
AC Under & Over Voltage
CHARGE FAILURE RELAY
3 A 30 V DC volt free relay
DSE9476
24 Volt 20 Amp Intelligent Battery Charger
183 mm x 233 mm x 76 mm (7.2” x 9.2” x 3.0”)
WEIGHT
1.8kg
PRODUCT VARIANTS
9476-01 - 24 V 20 A Intelligent Battery Charger
SPECIFICATION
AC SUPPLY
VOLTAGE RANGE
95 V to 305 V (L-N)
FREQUENCY RANGE
47 Hz to 63 Hz (L-N)
DC OUTPUT
DSE9476 OUTPUT
20 A DC at 24 V DC
RIPPLE AND NOISE
<1%
EFFICIENCY
>92%
REGULATION
LINE
<0.5%
LOAD
1%
TEMPERATURE SENSOR INPUT
PT1000
PROTECTIONS
Short Circuit
DC Under & Over Voltage
DC Over Current
Reverse Polarity
Over Temperature
AC Under & Over Voltage
CHARGE FAILURE RELAY
3 A at 30 V DC volt free relayOPERATING TEMPERATURE RANGE
-30 ˚C to +80 ˚C-22 ˚F to +176 ˚F
STORAGE TEMPERATURE RANGE
-40 ˚C to +85 ˚C-40 ˚F to +185 ˚F
DSE9474
24 Volt 30 Amp Intelligent Battery Charger
The DSE9474 is an intelligent 24-volt, 30 amp CAN enabled switch-mode battery charger that can be programmed for different charging curves. This helps to maximise battery life. The charger is programmed using the DSE Configuration Suite Software. The charger can be DIN rail or chassis mounted and has three built-in LEDs to indicate current charging status and fault conditions. The charger continues to operate during cranking and running and accepts multiple AC voltage connections.
240 mm x 263 mm x 89 mm (9.4” x 10.4” x 3.5”)
WEIGHT
2.5kg
PRODUCT VARIANTS
9474-01 - 24 volt 30 amp Intelligent Battery Charger (90-305v 50/60Hz)
SPECIFICATION
AC SUPPLY
VOLTAGE RANGE
90 V to 305 V (L-N)
FREQUENCY RANGE
48 Hz to 64 Hz (L-N)
DC OUTPUT
DSE9474 DC OUTPUT
30 A DC 24 V DC
RIPPLE AND NOISE
1%
>90%
REGULATION
LINE
<0.5%
LOAD
1%
TEMPERATURE SENSOR INPUT
PT1000
PROTECTIONS
Short CircuitDC Under & Over Voltage
DC Over Current
Reverse Polarity
Over Temperature
AC Under & Over Voltage
CHARGE FAILURE RELAY
3 A 30 V DC volt free relay
BC2410Ei
12/24 Volt 10 Amp Enclosed Intelligent Battery Charger
NFPA 110 (QWIR) COMPLIANT / UL LISTED
170 mm x 305 mm x 116 mm (6.7” x 12.0” x 4.6”)
WEIGHT
2.3kg
PRODUCT VARIANTS
BC2410Ei-01 - 12/24 Volt 10 Amp Enclosed Intelligent Battery Charger (Display)
BC2410Ei-02 - 12/24 Volt 10 Amp Enclosed Intelligent Battery Charger (Display & Meters)
BC2410Ei-03 - 12/24 Volt 10 Amp Enclosed Intelligent Battery Charger (Meters)
SPECIFICATION
AC SUPPLY
VOLTAGE RANGE
90 V to 305 V (L-N)
FREQUENCY RANGE
48 Hz to 64 Hz (L-N)
DC OUTPUT RATING
10 A DC at 12 & 24 V DC
RIPPLE AND NOISE
<1%
EFFICIENCY
>86%
REGULATION
LINE
<0.5%
LOAD
2%
TEMPERATURE SENSOR INPUT
PT1000
PROTECTIONS
Short Circuit
DC Over Voltage
DC Over Current
Reverse Polarity
Over Temperature
AC Under & Over Voltage
Battery Charger Failure
CHARGE FAILURE RELAY
3 A at 30 V DC volt-free relay
OPERATING TEMPERATURE RANGE
-30° C to +55° C-22° F to +131° F
OPERATING TEMPERATURE RANGE
(DE-RATE TO OUTPUT)
-30° C to +80° C-22° F to +176° F